High Voltage Power Factor Improving Panels for 10kV 20kV 36kV Power Distribution

High-voltage power factor correction (PFC) panels for 10kV, 20kV, and 36kV power distribution systems compensate for lagging reactive power caused by heavy industrial and utility loads like large motors, pumps, and transformers, High Voltage (HV) Power Factor Improving Panels (also known as High Tension/Medium Voltage Automatic Power Factor Correction or APFC Panels) are critical grid-grade components used in 10kV, 20kV, and 36kV electrical distribution networks. They improve system efficiency by injecting capacitive reactive power to offset inductive loads

Technical Parameter10kV System Configuration20kV System Configuration36kV System Configuration
Highest System Voltage (\(U_{m}\))12 kV24 kV36 kV / 40.5 kV
Rated Operational Frequency50 Hz / 60 Hz50 Hz / 60 Hz50 Hz / 60 Hz
Reactive Power Output Range150 kVAR ? 5,000 kVAR500 kVAR ? 10,000 kVAR1,000 kVAR ? 20,000+ kVAR
Power Frequency Withstand Voltage (1 min)28 kV ? 32 kV rms50 kV ? 60 kV rms75 kV ? 95 kV rms
Lightning Impulse Withstand Voltage (Peak)75 kV ? 95 kV125 kV ? 145 kV170 kV ? 200 kV
Step Switching ComponentVacuum Contactors / VCBsVacuum Contactors / VCBsVacuum Circuit Breakers (VCB)
Protection MechanismsHRC Fuses, RVT/NCT unbalanceHRC Fuses, RVT/NCT unbalanceMicroprocessor Relays, RVT protection
Enclosure Protection ClassIP40 / IP41 (Indoor)IP41 (Indoor) / IP54 (Outdoor)IP54 / IP55 (Weatherproof)
Applicable StandardsIEC 62271-200, IEC 60871IEC 62271-200, IEC 60871IEC 62271-200, IEC 60871